Permit Number: T05CM03367
Parcel: 11306185J

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM03367
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2005 GERRY KOZIOL WWM REVIEW Approved
08/12/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T05cm03367

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Provide ½" gypsum board on all walls common to the garage and house in compliance with R309.2.
2. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per figure R307.2.

Structural Plan and Elevations

1. 2/3 - dimension 6" grade to post.
2. Post to beam detail on elevations references detail 8/6. Clarify.
3. Detail 3/4 notes PC post cap while elevation depicts a corbel with lag bolt. Clarify post to beam connection.
4. Specify trusses over porch as 3-point bearing or resize porch beams. Current beam spans are too large for tributary width of a 2-point bearing truss.
5. (2) 2x10 header over SGD (8' span) in great room are inadequate. Resize.
6. Show calculation of attic ventilation area in compliance with R806.2.

Plumbing and Mechanical Plans

1. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down.
2. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
3. Note that bathtub and shower enclosures shall be finished per P2710 with ceramic tile, or a listed enclosure, to a height of 72" above the drain per R702.4 and R307.2.
4. How will furnace provide heating? Electric or gas? Show chosen method on respective plan and include in respective calculations.

MODEL ENERGY CODE:

1. Provide energy calculations per the 2000 IECC and comply with IRC chapter 11 or 'Rescheck' (www.energycodes.gov/rescheck/).
2. Call out on the plan the "R" values of insulation, as well as the "U" values of the windows and doors in compliance with the energy calculations provided. Windows must be low 'E'.

Outdoor Lighting Code

1. Show compliance with City of Tucson Outdoor Lighting Code (www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf).
2. Provide cut sheets of chosen lights.


If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.