Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM03350
Parcel: 111083580

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03350
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2005 JIM EGAN FIRE REVIEW Approved
07/06/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/06/2005 PATRICIA GEHLEN ZONING REVIEW Approved
07/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/08/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM03350 7/7/05

1. Identify a panel and circuit for the new ceiling fans.
2. Provide fault calculations to justify the 10,000K rating of new panels. If existing panels are rated for such, the Engineer may disregard this comment at his own discretion.
3. Provide AFCI protection for any new bedroom branch circuits. NEC 210.12 (B). Give consideration for such on existing circuits.
4. Identify a circuit for the new smoke detectors.
5. Provide a dedicated circuit for the bathroom per NEC 210.11 (C) (3).
6. Could not find Keynote 6 on the Typical Apartment Electrical Plan.
7. Specify that the new countertop receptacles shall be GFCI. NEC 210.8 (A) (6).
8. On the service load calculations, it would appear that only 1/2 of the units are 1016 SF, and the other half 849 SF.This SF has not been multiplied by 3 VA for both service load calculations.
9. For 8 dryers, it is permissable to use a demand factor of 60%, not 47%. NECTable 220.18.
10. 8-DW & DISP at (1200 + 720) = 1920 (5) 8 = 15360 (0.75) = 11,520 VA, not 16,800. NEC 220.17.
10. It appears that 16 DW/DISP would total 23,040VA, not 18000.
07/08/2005 ROBERT SHERRY WATER REVIEW Approved
07/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/13/2005 PATRICIA GILBERT ENGINEERING REVIEW Needs Review
07/19/2005 GERRY KOZIOL WWM REVIEW Approved