Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM03335
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/03/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Minimum 2-hour fire rated exterior wall required adjacent to west property line. Provide wall section/detail indicating minimum 30-inch parapet provided. 2. Provide fire sprinkler system design criteria on plan. |
| 11/04/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/04/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | needs to show location/methodof connection to public sewer. fronts 18" public sewer. needs 8th floor wastewater review |
| 11/07/2005 | SREEVES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/07/2005 | SUE REEVES | OUT TO CUSTOMER | Completed |