Permit Number: T05CM03307
Parcel: 130171470

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03307
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2005 JIM EGAN FIRE REVIEW Approved
07/05/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE LOADS, CALCULATIONS AND STRUCTURAL DETAIL FOR INSTALLATION OF KITCHEN HOOD.
07/05/2005 DAN CASTRO ZONING REVIEW Approved
07/05/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/26/2005 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
09/26/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03307 7/5/05

1. Minimum font size is 10 point, or 1/8".
2. Put load on panel schedule for A-23.
3. Coordinate with Mechanical for new Heat Pump. All Mechanical indicates is 2.6 FLA, which would be low. Electrical counts a total of 9880 VA, which would draw more than the 30A OCPDs would allow.
4. Please check loading on MAU-1. It apparently draws 25A according to the panel schedule, yet is protected by a 20A CB.
5. Please check loading on EF-1. It apparently draws 28A according to the panel schedule, yet is protected by a 20A CB.
09/26/2005 GBONILL1 WWM REVIEW Needs Review
09/26/2005 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
09/26/2005 GBONILL1 WATER REVIEW Needs Review