Permit Number: T05CM03307
Parcel: 130171470

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03307
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. The 20KW Duct Heaters would draw 55.6A. The 50A circuits do not appear to be adequate. THE DUCT HEATERS ARE ON CIRCUITS A-24,26,28 AND A-30,32,34 WHICH ARE PROTECTED BY 50A CIRCUIT BREAKERS.