| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. The 20KW Duct Heaters would draw 55.6A. The 50A circuits do not appear to be adequate. THE DUCT HEATERS ARE ON CIRCUITS A-24,26,28 AND A-30,32,34 WHICH ARE PROTECTED BY 50A CIRCUIT BREAKERS. |