Permit Number: T05CM03307
Parcel: 130171470

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03307
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/25/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide power for the water heater. Reference Sheet P2.
2. Please correct the total for Phase C on the Panel Schedule to read, 33,109, not 26,358. High phase amps appears to be 275A, not 242A.
3. The 20KW Duct Heaters would draw 55.6A. The 50A circuits do not appear to be adequate.
4. Mechanical revisions call for a 1 HP MAU-1, not the 1 ½ HP indicated on Sheet E2. It appears that this equipment will draw 8.8A. Please resize fusing at disconnect unless this is inherently overload protected.
10/02/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
10/06/2006 SUE REEVES REJECT SHELF Completed