Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/08/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/25/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide power for the water heater. Reference Sheet P2. 2. Please correct the total for Phase C on the Panel Schedule to read, 33,109, not 26,358. High phase amps appears to be 275A, not 242A. 3. The 20KW Duct Heaters would draw 55.6A. The 50A circuits do not appear to be adequate. 4. Mechanical revisions call for a 1 HP MAU-1, not the 1 ½ HP indicated on Sheet E2. It appears that this equipment will draw 8.8A. Please resize fusing at disconnect unless this is inherently overload protected. |
10/02/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved |