Permit Number: T05CM03307
Parcel: 130171470

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T05CM03307
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/31/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Coordinate the hood design elements as shown in the exhaust hood calculations, and the mechanical floor plan (e.g. the required airflow for the hood system is shown as 4800 CFM in the calculations and 3600 CFM in the schedules on sheet M2). If the hood is listed and labeled for use with heavy-duty cooking appliances at less than 4800 CFM, provide a cut-sheet from the hood manufacturer showing the listed airflow. Reference Sections 106.3.1 and 507.1, IMC 2003.
08/15/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 8/15/06
ACTIVITY NUMBER: T05CM03307
PROJECT NAME: La Fresita
PROJECT ADDRESS:1655 S. Alvernon Way
ARCHITECT / ENGINEER: Paul M. O'Connor
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Coordinate and justify structural calculations per the equipment location on mechanical plans. Provide all details required to carry the equipment loads.

2) Locate structural details SK1-SK4 on sht. 1 of 6 of structural calculations.

3) Provide and locate details SK1-SK4 on permit set. Show details on architectural drwgs. or provide structural drawings as a part of permit set.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/23/2006 VFLORES1 OUT TO CUSTOMER Completed
08/23/2006 SUE REEVES REJECT SHELF Completed