Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM03300
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2005 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T05CM03300

8/5/05 1651 E. LIND RD.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1. PLEASE INDICATE THE POWER TO THE EXISTING GUEST HOUSE AND THE EXISTING RESIDENCE. WILL THEY FEED A SUB-PANEL? ARE THEY TO BECOME SUB-PANELS? T.E.P. ALLOWS ONLY ONE CABLE DROP PER ADDRESS.

FOUNDATION:

1. FOUNDATION SCHEDULE NOTE 1 / 3 ; PLEASE REINFORCE THE TOP OF THE STEM WALL.

FLOOR PLANS:

1. "TIME LAPSE" …….WHAT'S A "TIME LAPSE" ROOM? PLEASE EXPLAIN THE USE.

2. "EQ. RACK"….PLEASE DESCRIBE THE "EQ".

3. WINDOWS ARE REQUIRED BY R303 AND OPENINGS ARE REQUIRED. THERE ARE SOME EXCEPTIONS. THE SKYLITES COULD BE COUNTED AS WINDOWS. DO THE SKYLITES OPEN? HOW ARE AIR CHANGES PROVIDED? TIME LAPSE ?

4. A 6' FIRE SEPARATION DISTANCE IS REQUIRED BY R302. IS THE EXISTING STORAGE BUILDING MASONRY OR ONE HOUR? IF THE MIKEY BLOCK IS ONE HOUR THEN A FIRE RATED DOOR WOULD DO THE TRICK. OR MOVE THE DOOR AWAY FROM THE STORAGE BUILDING.

STRUCTURAL PLANS:

1. PLEASE SIZE THE HIP RAFTERS (RIDGES).

2. PLEASE SIZE AND LOCATE THE SCUPPERS.

3. SPECIFY LUMBER GRADE AND SPECIES AND THE COMBINATION SYMBOL FOR THE GLUE LAMS.

4. PLEASE CHECK THE AVAILABILITY OF THE GLUE LAM SIZES THAT ARE SPECIFIED.

5. FRAMING / 4 ; PLEASE LABEL THE LOCATIONS OF THE "B1" BEAMS.

SECTIONS - DETAILS - MISC. NOTES:

1. 1 / 6 ; PLEASE GIVE THE ICF WALL FULL SUPPORT. SCOOT IT OVER THE STEM WALL.

2. 1 / 6 ; CLARIFY "2.5" - 25 GA. ALIGNMENT TRACK".

3. 2 / 6 ; THE REINFORCEMENT SHOWN IS FOR A CONTINUOUS FOOTING. CONTINUOUS OR PAD ?

4. 3 / 6 ; WHICH SERIES SIMPSON 66 POST CAP ? AC, BC, PC, CC, ETC. ?

5. 4 / 6 ; PLEASE SPECIFY THE JOIST HANGER.

6. 6 / 6 ; PLEASE PROVIDE A HOOK OR A BEND ON THE VERTICALS AT THE TOP OF THE WALL. SEE R611.7.1.2 .

7. LINTEL SCHEDULE / 6 ; HOW DEEP ARE THE LINTELS FOR THE 2' TO 4' SPANS ? ANY STIRRUPS ?

8. PLEASE PROVIDE AN OLSKI DETAIL SHOWING THE TWO PARTS. PROVIDE DIMENSIONS.

9. INSULATION SCHEDULE / 2 ; WHICH WINDOW U-VALUE IS TO BE USED? FIXED ? OPERABLE ?

10. 2 / 4 ; PLEASE SPECIFY THE ROOF SHEATHING AND ROOFING TYPE.

11. 2 (PLAN VIEW) / 4 ; # 3 IS THE MINIMUM TIE SIZE AND ISN'T PERMITTED TO BE WELDED. SEE ACI-318 .

12. 2 (PLAN VIEW) / 4 ; PLEASE PROVIDE BRICK TIES BETWEEN THE ADOBE VENEER AND THE GROUT COLUMN.

13. 2 / 4 ; PLEASE SPECIFY A BEAM SADDLE.

MECHANICAL PLANS:

1. RETURN AIR ISN'T PERMITTED TO BE TAKEN FROM A GARAGE. SEE M1602.2 ITEM 4.

2. PROVIDE 1 HOUR FIRE DAMPERS AND 26 GA. (MIN.) DUCTS FOR THE GARAGE.

3. PLEASE PROVIDE HEAT FOR THE "TIME LAPSE" ROOM. IS THE PROPOSED A/C A HEAT PUMP ?

ELECTRICAL PLANS:

1. TUCSON ELECTRIC ALLOWS ONE DROP PER ADDRESS. PLEASE PROVIDE LOAD CALCULATIONS ON THE EXISTING ELECTRIC SERVICE TO JUSTIFY THE ADDITIONAL LOAD.

2. I COULDN'T FIND CIRCUIT 17,19. HELP! PLEASE LOCATE!

3. ELECTRICAL NOTE 5 / 7 ; THE OUTDOOR LIGHTING CODE REQUIRES THE ENTIRE PROPERTY TO BE EVALUATED FOR THE OUTDOOR LIGHTING CODE IF THE FLOOR AREA OF THE ADDITION IS 25% OF THE ORIGINAL OR MORE. SEE SECTION 3.1.2 . ANY FULL CUT OFF FIXTURES? PROVIDE TOTAL LUMENS.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110