Permit Number: T05CM03160
Parcel: 13510150R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03160
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2005 JIM EGAN FIRE REVIEW Approved
06/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/28/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
06/28/2005 ROBERT SHERRY WATER REVIEW Approved
06/28/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
06/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/28/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
07/05/2005 GERRY KOZIOL WWM REVIEW Approved
07/05/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM03160 6/28/05

1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
2. It appears that circuits B-21 and B-23 both should have 2000 VA. Please re-evaluate.
3. Water Heater is 208/1/60, 4500W on Sheet P1. Is 1-P on Sheet E1 and 2500W on Panel Schedule. Coordinate with Plumbing and clarify.
4. New Heat Pump is 208/3/60 MCA 17.9 MOCP 25 on Sheet M1. Protected by a 50AF and 60ACB on electrical. Electrical load calcs appear high for 17.9 MCA.