Review Details: COMMERCIAL TI
Permit Number - T05CM03160
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/28/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/28/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/28/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/28/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 07/05/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/05/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM03160 6/28/05 1. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 2. It appears that circuits B-21 and B-23 both should have 2000 VA. Please re-evaluate. 3. Water Heater is 208/1/60, 4500W on Sheet P1. Is 1-P on Sheet E1 and 2500W on Panel Schedule. Coordinate with Plumbing and clarify. 4. New Heat Pump is 208/3/60 MCA 17.9 MOCP 25 on Sheet M1. Protected by a 50AF and 60ACB on electrical. Electrical load calcs appear high for 17.9 MCA. |