Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM03138
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Increase the size of the font to a minimum of 10 points. 2. Show cleanouts for the new sewer line. Reference Section 719, UPC 1994. 3. Show the slope of the sewer line. 4. Provide a detail of the termination of the new utilities. |
| 06/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03138 6/28/05 1. Indicate point of connection for sump pumps, with disconnects per NEC 430 Part IX. If cord-connected, specify receptacle on plans. 2. Provide lighting fixture schedule. Demonstrate compliance with Tucson Lighting Code, as applicable. 3. Indicate lighting fixtures on plans. 4. Provide receptacle locations on plans. 5. Indicate PH system on plans. Provide Code-compliant connection. 6. Indicate point of connection for pressure washers, with disconnects per NEC 430 Part IX. If cord-connected, specify receptacle on plans. 7. Applicant indicates that certain equipment is intended to be constructed with this project, and the remainder is future. If so, indicate which loads are future. |
| 07/06/2005 | KMEDINA1 | LANDSCAPE | REVIEW | Needs Review |