Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03097
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/01/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/01/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/01/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/01/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/01/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the outside air calculations per Section 403.3.2, IMC 2000. 2. Show how recirculation of the air from the restroom is to be prevented. Reference Section 403.2, IMC 2000. |
| 07/01/2005 | ANY | ENGINEERING | REVIEW | Approved | |
| 07/05/2005 | KMEDINA1 | WWM | REVIEW | Needs Review | |
| 07/05/2005 | KMEDINA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/05/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |