Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM03096
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/30/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/30/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | 1) CLARIFY DOOR INTO OTHER SUITE. ADDRESS COMBO REQUIRED. 2) PROVIDE VALUATION FOR THIS PROJECT. |
| 06/30/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/30/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 06/30/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/01/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/05/2005 | DROBEY1 | WWM | REVIEW | Passed | |
| 07/05/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM03096 6/30/05 1. Please clarify service. Six service disconnects are indicated on the line diagram, but there are 10 separate occupancies indicated on the title sheet. Amperages were indicated for the 6 disconnects on the line diagram, but none of them correspond to the subject 89A. Please indicate the capacity of the service in amps. |