Permit Number: T05CM03034
Parcel: 125100670

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T05CM03034
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a cut sheet for the proposed booster pump called out in detail 5/P-5. The specified total head of 14 GPM at 45 feet will not produce the required pressure of 60 PSIG at EF-2; are you sure the specified pump head isn't 14 GPM at 45 PSIG?

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
04/11/2007 SUE REEVES REJECT SHELF Completed