Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T05CM03034
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/05/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a cut sheet for the proposed booster pump called out in detail 5/P-5. The specified total head of 14 GPM at 45 feet will not produce the required pressure of 60 PSIG at EF-2; are you sure the specified pump head isn't 14 GPM at 45 PSIG? |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/11/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
04/11/2007 | SUE REEVES | REJECT SHELF | Completed |