03/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the provided water calculations, using the required static lift (19 feet) as required by Section A 1.1, UPC 1994.
2. Third request. Coordinate drawings P-3, P-4, and P-5 for the hot water piping to EF-2. Drawings P-3 and P-4 show 1-1/2" from WH-2 to EF-2 but drawing P-5 shows 1", 1-1/4", and 1-1/2" piping from WH-2 to EF-2. Also, detail 4/P-5 shows the booster pump being attached to WH-1, not WH-2.
3. Third request. Confirm the required drainage points for EF-2. Coordinate drawings P-2, P-4, and P-5 for the drains from EF-2. Drawing P-2 indicates 2 drains from EF-2 but drawings P-4 and P-5 show only one drain from EF-2.
4. Clarify the piping arrangement of the control box for EF-2.