02/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the provided water calculations, using the required static lift (19 feet) as required by Section A 1.1, UPC 1994.
2. Second request. Coordinate drawings P-3, P-4, and P-5 for the hot water piping to EF-2.
3. Second request. Confirm the required drainage points for EF-2. Coordinate drawings P-2, P-4, and P-5 for the drains from EF-2.
4. Clarify the location and piping arrangement of the control box for EF-2.
5. Provide calculations to show that the booster pump will provide 60 PSI at EF-2.
02/07/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved APPROVED PER ORIGINAL DETAIL DRAWINGS WITH LOAD PATH THROUGH WALL UNDER PLATFORM. CONFIRMED WITH FIELD STRUCTURAL OBSERVATION BY L HANLY AND CONVERSATION WITH EOR ON 2-7-07