Permit Number: T05CM03034
Parcel: 125100670

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T05CM03034
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specifications for the booster pump, P2, have changed from the approved drawings. Provide calculations and data to show that the new pump is capable of providing 6PSI water to EF-2. Reference Section 103.2.3, UPC 1994.
2. Provide structural calculations to show that the roof structure can support the addition of WH-2 (1340 Lb.). Reference Section 101.5.1, UPC 1994.
3. Provide a drip pan and drain for WH-2. Reference Section 510.7, UPC 1994.
4. Provide rain protection (i.e. a roof) for the indirect waste receptor located on the roof. Reference Sections 714.2 and D1.1(a), UPC 1994.
5. Confirm the required drainage points for EF-2. The approved plans show two 3" drains and a 1" drain but the revised plans show only two 3" drains.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2006 CINDY AGUILAR APPROVAL SHELF Completed
10/25/2006 CINDY AGUILAR OUT TO CUSTOMER Completed