Permit Number: T05CM03034
Parcel: 125100670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03034
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied The Booster Pump on Circuit C-37 Sheet E-2.1 is 1/3 HP. According to Detail 4 on Sheet P-5, this is to be a 1½ HP motor. The Mechanical Plans Examiner has confirmed that the Plumbing Plans call for the correctly sized motor. The concern is the starting of a 20A motor on a 20A circuit, and the correctness of the load calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/17/2006 ADRIANNE OLIVO OUT TO CUSTOMER Completed
05/17/2006 SUE REEVES REJECT SHELF Completed