Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/03/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | The Booster Pump on Circuit C-37 Sheet E-2.1 is 1/3 HP. According to Detail 4 on Sheet P-5, this is to be a 1½ HP motor. The Mechanical Plans Examiner has confirmed that the Plumbing Plans call for the correctly sized motor. The concern is the starting of a 20A motor on a 20A circuit, and the correctness of the load calculations. |