Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM03034
Parcel: 125100670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03034
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
03/16/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/16/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/11/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide power for P-1 Recirculating Pump and for P-2 Booster Pump. Reference Sheet P-5. Electrical provides a J-box and switch on Sheet E-6 for Hot Water Heater Pump with no further specification of intent. Could not be the
1 1/2 HP Booster Pump from the load on Circuit C-6.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/25/2006 GBONILL1 OUT TO CUSTOMER Completed
04/25/2006 SUE REEVES REJECT SHELF Completed