Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM03034
Parcel: 125100670

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM03034
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The details on sheet K-8 and the structural calculations (SC-11) indicate that the Type I hoods are mounted on combustible construction, a violation of Section 507.9, IMC 2000. Revise the structural calculations and details to show that the Type I hoods are either supported from non-combustible construction or have 18" clearance from combustible construction. Note that the IMC does not consider wood studs covered by gypsum board and stainless steel sheets to be non-combustible.
2. Provide the actual weights of the Type I hoods so that the structural calculations can be evaluated. Reference Section 106.3.1, IMC 2000.
3. Clarify the facilities requirements for MAU-1. A water connection for it is shown on sheets P-4 and P-5. If MAU does not have an evaporative cooler section, show how the make up air complies with Section 508.1.1, IMC 2000.
01/12/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide backflow protection for appliances (e.g. Ice machines, beverage dispensers, high pressure washer, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps. Reference Section 603.0, UPC 1994.
2. The note for the carbonator (#18) on sheet P-6 (plumbing fixture schedule) indicates a double check valve may be used instead of a reduced pressure backflow preventer and on sheet P-5 a double check valve is shown as protection for the carbonator. Only a reduced pressure backflow preventer is allowed for this use. Reference Section 603.3.12, UPC 1994.
3. The note for EF-2 on sheet P-6 (plumbing fixture schedule) indicates a reduced pressure backflow preventer is to be installed "if required by local authority". Design issues are not to be left to the contractor in the field.
4. Complete the specifications for the booster pump installed at the water heater (detail 4/P-5).
5. Provide the sizes for the roof drains and overflow drains for trellises and the covered trash enclosure shown on sheets A-14 and A-18. Coordinate the roof drainage with the architectural design. Reference Sections 103.2.3 and D1.1 (d), UPC 1994.
01/18/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied DATE: 12/12/05
ACTIVITY NUMBER: T05CM03034
PROJECT NAME: In-N-Out Burger3711 E. Broadway Blvd.
ARCHITECT / ENGINEER: Steven Langford
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

The following comments from 12/6/05 still have not been responded to on the drawings.

1) Provide structural calculations and details to show that the Type I hoods are supported. See Mechanical comments for further clarification.
2) Zoning needs to sign off before structural for clarification that the foot print of the building is not going to change. Also for clarification that the accessible path is not going to change.
3) Please note the layout of equipment for truss drawings and shop drawings do not match. Please submit new shop drawings or revise mechanical drawings.
01/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/23/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/28/2006 DAN CASTRO ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2006 GBONILL1 REJECT SHELF Completed