Permit Number: T05CM03018
Parcel: 11711080B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03018
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/23/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/23/2005 DAN CASTRO ZONING REVIEW Approved
06/23/2005 ROBERT SHERRY WATER REVIEW Approved
06/23/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/29/2005 JIM EGAN FIRE REVIEW Approved 1. Indicate type of locking hardware on all doors.
2. Building has fire sprinklers throughout, Indicate so on plan. A current fire sprinkler maintenance/inspection report is required.
3. Clarify occupancy classification(s) throughout.
4. Indicate occupant load for each floor.
5. Indicate fire rating of door 414 or fire rating of opening enclosure.
6. Show location of property lines.
08/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM03018 8/9/05

1. Identify panel and circuit number for all new receptacles.
2. Provide panel schedules and complete load calculations for any panels which power new receptacles.
3. Provide service load calculations as necessary.
12/02/2005 EGRANT1 WWM REVIEW Needs Review
12/02/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2005 BETH GRANT OUT TO CUSTOMER Completed