| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/23/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 06/23/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/23/2005 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 06/23/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/23/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/29/2005 | JIM EGAN | FIRE | REVIEW | Approved | 1. Indicate type of locking hardware on all doors. 2. Building has fire sprinklers throughout, Indicate so on plan. A current fire sprinkler maintenance/inspection report is required. 3. Clarify occupancy classification(s) throughout. 4. Indicate occupant load for each floor. 5. Indicate fire rating of door 414 or fire rating of opening enclosure. 6. Show location of property lines. |
| 08/09/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM03018 8/9/05 1. Identify panel and circuit number for all new receptacles. 2. Provide panel schedules and complete load calculations for any panels which power new receptacles. 3. Provide service load calculations as necessary. |
| 12/02/2005 | EGRANT1 | WWM | REVIEW | Needs Review | |
| 12/02/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/02/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |