Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM03005
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM03005
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/22/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
06/23/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/23/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/23/2005 ROBERT SHERRY WATER REVIEW Approved
06/23/2005 JIM EGAN FIRE REVIEW Approved
06/23/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/24/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
06/24/2005 GERRY KOZIOL WWM REVIEW Passed