Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM02989
Parcel: 10703140A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02989
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM02989 6/23/05
1. Identify upstream and downstream OCPDs in your series rating.
2. FLC of motors which could feed a fault shall not exceed 1% of rating of lower OCPD per NEC 240.86 (B).
06/24/2005 DAVID RIVERA ZONING REVIEW Approved
06/29/2005 GERRY KOZIOL WWM REVIEW Denied Needs 8th floor credit evaluation. Also contact addressing to correct Space #5 @ 740-6480.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2005 KMEDINA1 OUT TO CUSTOMER Completed