Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM02989
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/23/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM02989 6/23/05 1. Identify upstream and downstream OCPDs in your series rating. 2. FLC of motors which could feed a fault shall not exceed 1% of rating of lower OCPD per NEC 240.86 (B). |
| 06/24/2005 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 06/29/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs 8th floor credit evaluation. Also contact addressing to correct Space #5 @ 740-6480. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |