Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T05CM02885
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/23/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
06/23/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
06/24/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
06/24/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
06/24/2005 | ROBERT SHERRY | WATER | REVIEW | Passed | |
06/30/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide a complete single line diagram showing all conduit and conductor sizes,transformers,grounding, and over current protection,fault current etc. |
07/15/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | . City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) Page 8c of the calcs under STEM CONSTRUCTION shows top stem and 2nd stem. Under top stem is shown 2 foot stem and under 2nd stem is shown 0' , but theheight of wall is supposed to be 8.67 ft. Clarify! |