Permit Number: T05CM02885
Parcel: 12419079B

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM02885
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2005 JIM EGAN FIRE REVIEW Approved
06/23/2005 GERRY KOZIOL WWM REVIEW Passed
06/24/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/24/2005 ROBERT SHERRY WATER REVIEW Passed
06/30/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Provide a complete single line diagram showing all conduit and conductor sizes,transformers,grounding, and over current protection,fault current etc.
07/15/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied . City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Page 8c of the calcs under STEM CONSTRUCTION shows top stem and 2nd stem.
Under top stem is shown 2 foot stem and under 2nd stem is shown 0' , but theheight
of wall is supposed to be 8.67 ft. Clarify!

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2005 SUE REEVES OUT TO CUSTOMER Completed
07/26/2005 ANGIE SHOFFSTALL REJECT SHELF Completed