Permit Number: T05CM02881
Parcel: 13322500G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02881
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste fixture units for P4, P5, and P6 per Table 7-3 (commercial), UPC 1994.
2. Specify the type of backflow protection to be used for the icemaker. Reference Section 603.0, UPC 1994.
3. Revise the detail 4/P1.2 to show the hot water connected to the left side of the fittings for P-6 in the bag prep area. Reference Section 601.2, UPC 1994.
4. Clarify what is happening to the piping for P-4 on the water isometrics. Reference Section 103.2.3, UPC 1994.
5. Revise the roof drainage calculations to limit the head at the weir to no more than 2" above the low point of the roof for the primary drainage flow. Reference Appendix D 1.1 (d), UPC 1994.
07/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Terminate condensate drains in accordance with Section 307.2.1, IMC as amended by the City of Tucson. The condensate drains may terminate at the tailpiece of a lavatory or a drinking fountain but not at a sink.
07/18/2005 EGRANT1 WWM REVIEW Needs Review