Permit Number: T05CM02881
Parcel: 13322500G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02881
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Calculate the water demand using the public fixture units shown in Tables 6-3 or A-2. Reference Section 610.3, UPC 1994.
2. The minimum residual water pressure shall be 15-PSI. Reference Section 608.1, UPC 1994.
3. Confirm that the icemaker is operable on a minimum pressure of 15-PSI. Revise calculations as necessary. Reference Section 608.1, UPC 1994.
4. Revise the detail 4/P1.2 to show the hot water connected to the left side of the fittings for P-6 in the bag prep area. (Note that the Fixture Schedule also shows P-8 being fed with hot water.) Reference Section 601.2, UPC 1994.
5. Provide waste and vent isometrics. Reference Section 103.2.3, UPC 1994.
6. Provide calculations to show that the roof is adequately drained. Reference Appendix D, UPC 1994.
06/23/2005 ROBERT SHERRY WATER REVIEW Approved
06/24/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
06/24/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation using Section 403.3, IMC or file an appeal to the building official requesting permission to use ASHRAE Standard 62-2002 (n). Reference Section 401, IMC 2000.
2. The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5. Reference Section 803.2.8, IECC 2000.
3. Provide the installed weights for the existing rooftop air conditioners and if they are lighter than the new units, provide calculations to show that the roof can support the new loads.
4. Show the size, routing, and termination of the condensate drain for AC-3. Reference Section 307.2, IMC 2000 and Section 807.2, UPC 1994.
5. Terminate condensate drains in accordance with Section 307.2.1, IMC as amended by the City of Tucson.
07/07/2005 STANTEC ELECTRICAL-COMMERCIAL REVIEW Approved
07/14/2005 JMORALE1 WWM REVIEW Needs Review