Permit Number: T05CM02877
Parcel: 134234110

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02877
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/01/2005 CRAIG GROSS ZONING REVIEW Approved
11/03/2005 GERRY KOZIOL WWM REVIEW Approved
11/08/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM02877 .. 6320 E BROADWAY BLVD .. 3rd REVIEW .. DGL .. 11/10/05 ..

S1.Clarify drawings to be part of this set, as "INDEX OF DRAWINGS" on drawing G1 indicates the following drawings form this set :
G-1 GENERAL NOTES
A-1 ARCHITECTURAL FLOOR PLAN
M-1 MECHANICAL PLAN
M-2 MECHANICAL DETAILS / DIAGRAMS / NOTES
P-1 PLUMBING PLANS
P-2 PLUMBING DETAILS / DIAGRAMS / NOTES,
though only drawings : G-1, A-1, M-1,P-1 AND D-1 have been resubmitted (drawings M-2 and P-2 are missing from this re-submittal and drawing D-1 has been added) for this review, please update index of drawings and provide drawings per your index to clarify, ref 1997 Uniform Administrative Code Section 302.
S2. See prior comment #S1.

1. Clarify validity of permit, per UAC Section 303.3. [1. As this Permit divides this building and adjacent tenant space (6318 E Broadway Blvd) was issued a Certificate of Occupancy based on having access to the toilet rooms present in this space (6320 E Broadway Blvd), explain and show how adequate access to toilet rooms will be provided for the adjacent space (6318 E Broadway Blvd).]
2. Provide two accessible toilet facilities per IBC Section 2902.2 and Occupant load of 19. [2. Provide minimum plumbing fixtures as required by IBC Section 29.]
3. Indicate fastening to bracing and to structure above with fastener type, size, spacing /number, ref 3/D-1. [3. Detail wall at washer/dryer.]
4. Provide infill detail showing materials of construction , including fastening to structure indicating fastener type, size, spacing/number. [4. Detail infill at door #120L.]
5. Where is door schedule referred to in detail 7/D-1, provide door information, including door size and hardware , per IBC Section 10 and 11. [5. Detail new door at Therapy/Massage Room w/private shower.]
6. Provide infill detail showing materials of construction , including fastening to structure indicating fastener type, size, spacing/number. [6. Detail new wall between Therapy/Massage Rooms.]
7. Where is door schedule referred to in detail 7/D-1, provide door information, including door size and hardware, show therapy/shower conformance to accessibility requirements, per IBC Section 10, 11and 34. [7. Detail new door at private shower.]
8. OK per 1/D-1.[8. Detail removal of vanity area wall and two lavatories located in Vanity Area ,Room #123.
9. Where is door schedule referred to in detail 7/D-1, provide door information, including door size and hardware, dimension toilet room floor plan to show conformance,per IBC Section 10 and 11. [7. Detail remodel of Restroom #124, including removal of water closet, installation of lavatory and grab bars, etc.]
[ S1. See prior comment #S2. (S2. Provide information to permit changes from prior permitted drawings, including employee restroom, wall relocated at washer/ dryer, change of manicure room to shampoo room, relocation of wall shown on prior permitted drawings at plan west wall of accessible toilet room (this area appears to be extensively different than prior approved plans show changes as part of this remodel, revise as necessary to meet current code and permit), explain therapy intended to take place in therapy rooms on drawings, etc.). Referenced plan is prior plan COT Building Permit #129318 for Cele Peterson by Intertech in 1995.
1. As this Permit divides this building and adjacent tenant space (6318 E Broadway Blvd) was issued a Certificate of Occupancy based on having access to the toilet rooms present in this space (6320 E Broadway Blvd), explain and show how adequate access to toilet rooms will be provided for the adjacent space (6318 E Broadway Blvd).
2. Provide minimum plumbing fixtures as required by IBC Section 29.
3. Detail wall at washer/dryer.
4. Detail infill at door #120L.
5. Detail new door at Therapy/Massage Room w/private shower.
6. Detail new wall between Therapy/Massage Rooms.
7. Detail new door at private shower.
8. Detail removal of vanity area wall and two lavatories located in Vanity Area ,Room #123.
9. Detail remodel of Restroom #124, including removal of water closet, installation of lavatory and grab bars, etc.
Massage facilities have specified requirements per Tucson City Code Article VII. Massage Establishments, Sec. 7-137. Massage establishment license; inspections., show conformance to these requirements. See attachment or Tucson City Code online at www.tucsonaz.gov.]
S3. See prior comment #S2. Provide second toilet room per IBC Section 2902.2 and Table 2902.1, based on Occupant load of 19 per IBC Section 1004, table 1004.1.2 (1901sf/100 gross = Occupant load of 19). {S2. See prior comment #S3 or provide second toilet room in this suite conforming to accessibility requirements of IBC Section 1109.2.1 and ANSI A117.1-2003ed, per IBC Section 29. [S3. Show access to employee restroom as well as restroom is maintained (see prior permit set)].}.
S3. See prior comment #S4, show where 20% of Project Valuation is spent on accessibility. (S4. Address accessibility, per IBC Sec 34.)

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.