Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM02877
Parcel: 134234110

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02877
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Second request. Confirm that the four reduced pressure backflow preventers conform to the access and clearance requirements of Section 603.2.3, UPC 1994 and include the clearance dimensions on the drawing. Note: If each RPBP requires 12" of clearance below the valve assembly and the height of each valve is 4-5/8", the highest valve will be located over 5'-0" above the floor.
08/10/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
08/19/2005 GERRY KOZIOL WWM REVIEW Denied Recounted all plumbing fixtures. Needs 8th Fl credit evaluation.
09/08/2005 DAN CASTRO ZONING REVIEW Denied Since the last approved use for this space is Retail (CofO 1995), a shopping center calculation and tenant list must be provided to verify compliance with vehicle parking requirements. The list shall include the tenant name, space number or address, land use classification, vehicle parking ratio required, number of vehicle parking spaces required, and total number of vehicle parking spaces required and provided for the shopping center. For additional information please contact me at 791-5608 ext. 1180.
09/12/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM02877-1 .. 6320 E BROADWAY BLVD .. 2nd REVIEW .. DGL .. 9/14/05 ..

S1. See prior comment #S2. (S2. Provide information to permit changes from prior permitted drawings, including employee restroom, wall relocated at washer/ dryer, change of manicure room to shampoo room, relocation of wall shown on prior permitted drawings at plan west wall of accessible toilet room (this area appears to be extensively different than prior approved plans show changes as part of this remodel, revise as necessary to meet current code and permit), explain therapy intended to take place in therapy rooms on drawings, etc.). Referenced plan is prior plan COT Building Permit #129318 for Cele Peterson by Intertech in 1995.
1. As this Permit divides this building and adjacent tenant space (6318 E Broadway Blvd) was issued a Certificate of Occupancy based on having access to the toilet rooms present in this space (6320 E Broadway Blvd), explain and show how adequate access to toilet rooms will be provided for the adjacent space (6318 E Broadway Blvd).
2. Provide minimum plumbing fixtures as required by IBC Section 29.
3. Detail wall at washer/dryer.
4. Detail infill at door #120L.
5. Detail new door at Therapy/Massage Room w/private shower.
6. Detail new wall between Therapy/Massage Rooms.
7. Detail new door at private shower.
8. Detail removal of vanity area wall and two lavatories located in Vanity Area ,Room #123.
9. Detail remodel of Restroom #124, including removal of water closet, installation of lavatory and grab bars, etc.
10. Massage facilities have specified requirements per Tucson City Code Article VII. Massage Establishments, Sec. 7-137. Massage establishment license; inspections., show conformance to these requirements. See attachment or Tucson City Code online at www.tucsonaz.gov.
S2. See prior comment #S3 or provide second toilet room in this suite conforming to accessibility requirements of IBC Section 1109.2.1 and ANSI A117.1-2003ed, per IBC Section 29. [S3. Show access to employee restroom as well as restroom is maintained (see prior permit set).]
S3. See prior comment #S4, show where 20% of Project Valuation is spent on accessibility. (S4. Address accessibility, per IBC Sec 34.)

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
09/19/2005 SUE REEVES REJECT SHELF Completed