Permit Number: T05CM02877
Parcel: 134234110

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02877
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2005 JIM EGAN FIRE REVIEW Approved
06/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Confirm that the four reduced pressure backflow preventers conform to the access and clearance requirements of Section 603.2.3, UPC 1994 and include the clearance dimensions on the drawing.
2. Provide indirect waste piping for the discharges of the reduced pressure backflow preventers to an approved indirect waste receptor.
3. Confirm that the location of the floor sink by the pedicure tubs is readily accessible and complies with the requirements of Section 804.1, UPC 1994.
4. Provide information to confirm that the reduced pressure backflow preventers for hot water service are listed for operation with water temperatures of at least 110 degrees Fahrenheit. Reference Section 603.2.5, UPC 1994.
06/24/2005 ROBERT SHERRY WATER REVIEW Approved
06/24/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/29/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/30/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied Provide elec. plan for T.I. or provide the last approved elec floor plan showing all the existing electrical that you are now utilizing.
07/14/2005 GERRY KOZIOL WWM REVIEW Denied Recounted all plumbing fixtures. Needs 8th Fl credit evaluation.
07/18/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM02877 .. 6320 E BROADWAY BLVD .. 1ST REVIEW .. DGL .. 7/19/05 ..

S1. Clarify key map/site/location plan and clearly show location of tenant space, on drawings.
S2. Provide information to permit changes from prior permitted drawings, including employee restroom, wall relocated at washer/ dryer, change of manicure room to shampoo room, relocation of wall shown on prior permitted drawings at plan west wall of accessible toilet room (this area appears to be extensively different than prior approved plans show changes as part of this remodel, revise as necessary to meet current code and permit), explain therapy intended to take place in therapy rooms on drawings, etc.
S3. Show access to employee restroom as well as restroom is maintained (see prior permit set).
S4. Address accessibility, per IBC Sec 34.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
07/25/2005 DAN CASTRO ZONING REVIEW Denied 1. Provide a copy of the last approved CofO for this address (tenant space). If the CofO is not provided or if the last CofO is for a use requiring less parking than the proposed use, a vehicle parking inventory for the shopping center shall be provided for review. The inventory shall include every tenant name, space number or address, gross floor area, land use classification with vehicle parking ratio required, vehicle parking spaces required, and number of vehicle parking spaces provided for the overall shopping center.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2005 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed
07/25/2005 ANGIE SHOFFSTALL REJECT SHELF Completed