Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02877
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/24/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Confirm that the four reduced pressure backflow preventers conform to the access and clearance requirements of Section 603.2.3, UPC 1994 and include the clearance dimensions on the drawing. 2. Provide indirect waste piping for the discharges of the reduced pressure backflow preventers to an approved indirect waste receptor. 3. Confirm that the location of the floor sink by the pedicure tubs is readily accessible and complies with the requirements of Section 804.1, UPC 1994. 4. Provide information to confirm that the reduced pressure backflow preventers for hot water service are listed for operation with water temperatures of at least 110 degrees Fahrenheit. Reference Section 603.2.5, UPC 1994. |
| 06/24/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/24/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/29/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 06/30/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide elec. plan for T.I. or provide the last approved elec floor plan showing all the existing electrical that you are now utilizing. |
| 07/14/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | Recounted all plumbing fixtures. Needs 8th Fl credit evaluation. |
| 07/18/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T05CM02877 .. 6320 E BROADWAY BLVD .. 1ST REVIEW .. DGL .. 7/19/05 .. S1. Clarify key map/site/location plan and clearly show location of tenant space, on drawings. S2. Provide information to permit changes from prior permitted drawings, including employee restroom, wall relocated at washer/ dryer, change of manicure room to shampoo room, relocation of wall shown on prior permitted drawings at plan west wall of accessible toilet room (this area appears to be extensively different than prior approved plans show changes as part of this remodel, revise as necessary to meet current code and permit), explain therapy intended to take place in therapy rooms on drawings, etc. S3. Show access to employee restroom as well as restroom is maintained (see prior permit set). S4. Address accessibility, per IBC Sec 34. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111. |
| 07/25/2005 | DAN CASTRO | ZONING | REVIEW | Denied | 1. Provide a copy of the last approved CofO for this address (tenant space). If the CofO is not provided or if the last CofO is for a use requiring less parking than the proposed use, a vehicle parking inventory for the shopping center shall be provided for review. The inventory shall include every tenant name, space number or address, gross floor area, land use classification with vehicle parking ratio required, vehicle parking spaces required, and number of vehicle parking spaces provided for the overall shopping center. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/25/2005 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |
| 07/25/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |