Permit Number: T05CM02838
Parcel: 129010330

Address:
236 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02838
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
06/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagams for the water piping and waste & vent piping.
2. The hand sink, 2-compartment sink, and the work table sink must be directly connected to the sanitary drain.
3. Provide information to show that a grease interceptor is not required.
06/24/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied
06/24/2005 ROBERT SHERRY WATER REVIEW Approved
06/24/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a Type 1 hood for the ranges. Provide structural calculations and details for the support of the hood. Reference Sections 507.2.1 and 507.2.2, IMC 2000.
2. Show that the makeup air complies with Section 508.1.1, IMC 2000.
06/28/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/01/2005 JIM EGAN FIRE REVIEW Denied 1. Clarify occupancy classification I-4 or A-3 Adult Day Care?
2. Show location of minimum one hour fire rated exit corridor.Openings protected with minimum 20-minute rated fire assemblies.
3. Type 1 exhaust hood and fire suppression system required for cooking ranges.
09/09/2005 JMORALE1 WWM REVIEW Needs Review
09/09/2005 JMORALE1 ZONING REVIEW Needs Review