Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM02835
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | NON-SUBSTANTIAL IMPROVEMENT Date: September 20, 2005 Address: 3901 East Speedway Blvd. Permit Numbers: T05CM02835/T05OT02313 Floodplain type: City of Tucson Description of Work: Tenant Improvment Type permit: Non-residential Year of construction of existing structure: 1978 Value of work: $ 60,800 Prior permit activity value $ 0 Value of structure: $ 396,400 Increase in Flood Damage Potential: % 15 |
| 10/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference Section 103.2.3, UPC 1994. 2. Provide fixture descriptions for all new plumbing fixtures. Reference Section 103.2.3, UPC 1994. |
| 10/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the ventilation for the modified restrooms complies with Section 403.3, IMC 2000. 2. The Code Review Notes on sheet A1.1 refer to mechanical work for this project; Show all mechanical work (e.g. relocation of diffusers) on the drawings. Reference Section 106.3.1, IMC 2000. |
| 10/17/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Cross-reference locations where the new lintels are being located. (SK2 and SK3) |