Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T05CM02790
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2005 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | Submit last approved site plan to continue review. |
| 10/04/2005 | ANDREW CONNOR | NPPO | REVIEW | Approved | Exception |
| 10/05/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/21/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | Floodplain Use Permit: T05CM02433 Not a substantial improvement Existing Structure: $54,440 Improvements: $20,300 |
| 10/24/2005 | DAN CASTRO | ZONING HC SITE | REVIEW | Denied | See Zoning Review comments. |
| 10/24/2005 | DAN CASTRO | ZONING | REVIEW | Denied | 1. A minimum four (4) foot sidewalk is required between the restroom addition and the vehicle parking spaces. The sit plan is currently showing only three (3) feet. 2. Provide a copy of the most recent approved site plan for reference. The vehicular use area appears to encorach into public right-of-way area (i.e. wash area). Additional comments may be forthcoming. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/27/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/27/2005 | CINDY AGUILAR | REJECT SHELF | Completed |