Permit Number: T05CM02790
Parcel: 11015123B

Address:
5563 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02790
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2005 GERRY KOZIOL WWM REVIEW Approved
10/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Registrant shall sign and date plans.
2. Provide panel and circuit numbers for all new new electrical equipment.
3. Provide a disconnect for the new WH per NEC 422 Part III.
4. Provide panel schedule and load calculations.
10/21/2005 LOREN MAKUS ENGINEERING REVIEW Approved Floodplain Use Permit: T05CM02433
Not a substantial improvement
Existing Structure: $54,440
Improvements: $20,300
10/24/2005 DAN CASTRO ZONING REVIEW Denied Building plans must be approved by structural review and site plan must be approved by all sections prior to zoning review sign-off of building plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
10/27/2005 BILL MARUM REJECT SHELF Completed