Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Registrant shall sign and date plans. 2. Provide panel and circuit numbers for all new new electrical equipment. 3. Provide a disconnect for the new WH per NEC 422 Part III. 4. Provide panel schedule and load calculations. |
10/21/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | Floodplain Use Permit: T05CM02433 Not a substantial improvement Existing Structure: $54,440 Improvements: $20,300 |
10/24/2005 | DAN CASTRO | ZONING | REVIEW | Denied | Building plans must be approved by structural review and site plan must be approved by all sections prior to zoning review sign-off of building plans. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/27/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
10/27/2005 | BILL MARUM | REJECT SHELF | Completed |