Permit Number: T05CM02790
Parcel: 11015123B

Address:
5563 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02790
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2005 TERRY STEVENS ZONING REVIEW Needs Review
09/30/2005 KMEDINA1 WWM REVIEW Needs Review
09/30/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/30/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02790 9/30/05

Plans changed in scope of work before permit issued. Needs completely new review.

1. N/A.
2. Provide panel and circuit number for all new electrical loads.
3. Plot location of electrical panel on plans.
4. Provide panel schedule, with load calculations.
5. Provide disconnect for new Water Heater per NEC 422 Part III.
09/30/2005 PATRICIA GILBERT ENGINEERING REVIEW Needs Review
09/30/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
09/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved 1. Show how the water lines to the new restroom
were sized. Provide water pressure calculations and show that the ¾" pipes to the water heater will be able to handle the new load.
2. The upper terminal cleanout for the water closet needs to be sized per Section 707.11, UPC 1994.
3. Provide an additional cleanout for the building sewer from the new restroom due to the aggregate horizontal change of direction of over 135 degrees. Reference Section 719.1, UPC 1994.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2005 KMEDINA1 OUT TO CUSTOMER Completed