Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02790
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/17/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify what is being done with the grease trap. 2. Show how the water lines to the new restroom were sized and indicate the size of the pipes to whichthey are being connected. 3. Provide an upper terminal cleanout for the water closet. reference Section 707.4, UPC 1994. 4. Show the route of the building sewer from the new restroom to the connection to the "existing main". Show all required cleanouts per Section 707.4, UPC 1994. |
| 06/17/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CODE ANALYSIS DATA SHT. 2) PROVIDE OCCUPANT LOAD OR SEATING PLAN FOR CLARIFY QUANTITY OF FIXTURES REQUIRED. 3) CLARIFY ACCESSIBLE PATH TO RESTROOM FACILITIES. 4) PROVIDE VALUATION / COST OF CONSTRUCTION FOR THIS PROJECT. |
| 06/17/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/17/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Plans changed in scope of work before permit issued. Needs completely new review. |
| 06/17/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the exhaust fan provides at least 75 CFM of exhaust per Section 403.3, IMC 2000. |
| 07/11/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 07/11/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 07/11/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Needs Review |