Permit Number: T05CM02767
Parcel: 129090420

Address:
1520 E 25TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG-MODEL PLAN/ENGINE/WALK THRU

Permit Number - T05CM02767
Review Name: RESIDENTIAL BLDG-MODEL PLAN/ENGINE/WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/16/2005 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
06/17/2005 MICHAEL ST. PAUL ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Michael St.Paul FOR: David Rivera
Planning Technician Principal Planner

PROJECT:
T05CM02767
1520 E 25th Street
Comments for full code compliance and BOA variance application
TRANSMITTAL: June 17, 2005
DUE DATE: June 17, 2005


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/
DEVELOPMENT
STANDARD

1. This is a full code compliance review for three units in the R-2 zone. The Development Designator is "K" and the Perimeter Yard Indicator is BB. This site is required to meet commercial standards.
LUC Sec 2.3.5.2.A.2, 3.2.3.1.B & 3.2.6.4
2. All parking and maneuvering for vehicle use areas must be provided within the site boundaries. The current parking configuration on the north property line must be revised so that there is sufficient maneuvering area so that cars do not back out into the street.
LUC Sec 3.3.7.5 &
3. All parking areas must have direct access to a public or private street or via an easement. The south parking lot does not have appropriate access.
LUC Sec 3.2.8.2
4. Landscaping and screening is required for all vehicle use areas. A ten foot (10') landscaping area is required along the north property line. Additional landscape comments will be provided in the landscape review. (See comment #7.)
LUC Sec 3.3.7.7
5. The back-up spurs in the south parking lot must provide a minimum of three feet to the property line.
DS 3-05.2.2.D
6. Please provide proper dimension on the elevations so that the heights listed can be confirmed. The north and south wall on the model plan scale out to be twelve feet (12') measured from ground to the highest point of the wall. Please provide dimensions on all elevations.
LUC Sec 3.2.6.4
7. A Landscaping review is required.

8. Please be aware that additional comments may be required due to alterations of the plans.
06/23/2005 ANDREW CONNOR NPPO REVIEW Denied Submit NPPO plan or application for exception.