Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02761
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/20/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/20/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/20/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the plumbing schedule with the plans and riser diagrams (i.e. how many water closets are to remain?). 2. Provide a CW shut off valve for the building entrance. Reference Section 605.3, UPC 1994. 3. Calculate the water demand using the fixture units shown in Tables 6-3 or A-2 (e.g. P-4 and P-7). Reference Section 610.3, UPC 1994 4. Confirm that the proposed ¾" water meter is listed for the calculated demand. Reference Section 610.2, UPC 1994. 5. Provide special inspection for the medical gas piping. 6. Provide operating and listing information for the medical vacuum pump. Provide electrical power to the vacuum pump. Reference Section 103.2.3, UPC 1994. 7. Clarify the note regarding the connection of the discharge of the medical vacuum pump to the existing sanitary vent and show how it meets the requirements of NFPA 99. |
| 06/29/2005 | KMEDINA1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/29/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |