Permit Number: T05CM02761
Parcel: 13421093A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02761
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/20/2005 ROBERT SHERRY WATER REVIEW Approved
06/20/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/20/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing schedule with the plans and riser diagrams (i.e. how many water closets are to remain?).
2. Provide a CW shut off valve for the building entrance. Reference Section 605.3, UPC 1994.
3. Calculate the water demand using the fixture units shown in Tables 6-3 or A-2 (e.g. P-4 and P-7). Reference Section 610.3, UPC 1994
4. Confirm that the proposed ¾" water meter is listed for the calculated demand. Reference Section 610.2, UPC 1994.
5. Provide special inspection for the medical gas piping.
6. Provide operating and listing information for the medical vacuum pump. Provide electrical power to the vacuum pump. Reference Section 103.2.3, UPC 1994.
7. Clarify the note regarding the connection of the discharge of the medical vacuum pump to the existing sanitary vent and show how it meets the requirements of NFPA 99.
06/29/2005 KMEDINA1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2005 KMEDINA1 OUT TO CUSTOMER Completed