Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2005 JIM EGAN FIRE REVIEW Approved
06/16/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/16/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
06/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02761 6/16/05

1. Sheet E-2 could not find Keynote 11 on plans.
2. Sheet E-2 there is a dosconnect with no panel/circuit designation, upper right.
3. Keynote 3 Sheet E-2 does not appear to apply to new W/D. Also, add panel and ckt # for this new load.
4. Provide panel and circuit number for new sink receptacle(s).
5. Minimum font size 1/8".
6. Add 25% for largest motor on Panel B load tabulation.
7. 17A on Panel B (schedule) is incorrect. Revise, and carry through to service load calculations.
8. If Panel B is on a 150A feeder, that feeder would not be protected by a 200A OCPD.
9. If Panel B is on a 150A feeder, it would not be sufficient for the load.

Second review 6/16/95 still needed corrections #1,2, & 6 above.