Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02746
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/15/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 06/15/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The size of the water pipe supplying the new restroom is undersized based on the provided calculations. (Note that the calculations are also incorrect). Reference Section 610.4, UPC 1994. 2. Provide a detail showing the installation of the water heater, including an expansion tank,T&P relief, and shutoff valve. 3. Provide a cleanout for the water closet. |
| 06/15/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/15/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/15/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/15/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/15/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02746 6/15/05 1. Provide a disconnect for the new Water Heater Per NEC 422 Part III, or justify otherwise. 2. Add the following note in a prominent place: "All work in patient care areas shall comply with NEC 517.13." |
| 06/16/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/16/2005 | GBONILL1 | ZONING | REVIEW | Needs Review |