Permit Number: T05CM02746
Parcel: 10510062G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02746
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2005 JIM EGAN FIRE REVIEW Approved
06/15/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The size of the water pipe supplying the new restroom is undersized based on the provided calculations. (Note that the calculations are also incorrect). Reference Section 610.4, UPC 1994.
2. Provide a detail showing the installation of the water heater, including an expansion tank,T&P relief, and shutoff valve.
3. Provide a cleanout for the water closet.
06/15/2005 ANY BUILDING-COMMERCIAL REVIEW Approved
06/15/2005 ROBERT SHERRY WATER REVIEW Approved
06/15/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/15/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02746 6/15/05
1. Provide a disconnect for the new Water Heater Per NEC 422 Part III, or justify otherwise.
2. Add the following note in a prominent place: "All work in patient care areas shall comply with NEC 517.13."
06/16/2005 GERRY KOZIOL WWM REVIEW Approved
06/16/2005 GBONILL1 ZONING REVIEW Needs Review