Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM02745
Parcel: 123041350

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM02745
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2005 GERRY KOZIOL WWM REVIEW Denied need to review location of connection to pubic sewer in street.
07/25/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T05cm02745

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Provide access to each separate attic space that exceeds 30SF per R807. Designate locations on the drawings. Openings shall not be less than 22"X30" for attics. Attic access shall provide a minimum of 30" of headroom, and shall be located in a hallway or readily accessible space.
2. Note and specify that shower enclosures shall have a minimum finished interior area of 1,024 square inches and shall be capable of encompassing a minimum 30" circle per 1994 UPC SEC. 410.0. All glass enclosures shall be tempered.
3. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per figure R307.2.
4. MEC - R-values for insulation on plan do not match calculations. Also, R-30 will not fit into 2x6 wall space. Specify R-19 in 2x6 walls on plans and in calculations.

Structural Plan

1. Braced wall - 4' panel will not fit at corner behind wet bar. Re-locate to other side of wet bar window. Also - If building will be fully sheathed, note this and disregard labeling braced wall panels.
2. Detail references on Framing and Foundation plan are incorrect.
3. Is concrete stoop footing to be the same as the house bearing footing? A simple turndown is sufficient.
4. Detail 1/3 and 3/3 note 2x4 walls. General note #1 (pg 2) and Framing note #2 (pg. 2) note 2x6 walls. Clarify and revise insulation value to R-13 if using 2x4 wall.
5. Fixed Section, page 3, does not represent actual trussed roof. Revise.
6. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.
7. 3/3 - How is facia attached to trusses?
8. 2/3 - Clarify what this detail represents.
9. When using 1/2" sheetrock on ceiling with rafters or trusses spaces at 24"o/c, use the sag resistant type per table R702.3.5. Specify.
10. Detail gable end bracing and it's connections to structure.

Electrical Plan

1. Bath circuit #13 is noted as 'Spare' on panel schedule. Revise.
2. Show water heater outlet on plan.
3. Circuit #15 is blank on panel schedule but shown as a receptacle circuit on plan.
4. Will main panel on house be an "Upgrade"?
5. Size feeders to sub-panel and note sup-panel amperage (current panel schedule notes 200amp which is too big to be fed from a 200amp main panel.
6. Show location of sub-panel.
7. Load calculations do not reflect the appliances in this guesthouse. Calculations must be provide for both the main house and the guesthouse separately to ensure that the guesthouse load does not exceed the sub-panel's ampacity and the total load does not exceed the main panel's ampacity.
8. Is the wall mounted AC/ heater really require 50amp, 220v circuit? Clarify and show disconnect for unit on plan.

Plumbing Plan

1. Size all vents.
2. Note that sewer line will be 2' away from footing that are parallel with line.
3. Not total developed length (meter to furthest fixture) for water supply line.
4. Fixture schedule seems a bit scant in respect to the amount of existing fixtures. Verify that this schedule reflects the total (new and existing) fixtures that will be served by the same water meter.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2005 JMORALE1 OUT TO CUSTOMER Completed
07/26/2005 ANGIE SHOFFSTALL REJECT SHELF Completed