Permit Number: T05CM02696
Parcel: 107110010

Address:
3175 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02696
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2005 JIM EGAN FIRE REVIEW Approved
08/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994.
2. Provide site drawing showing the size, route, and termination of the building sewer. Reference Section 103.2.3, UPC 1994.
3. Provide the minimum plumbing facilities (e.g. drinking fountain) required by Table 2902.1, IBC 2003, for business occupancy.
4. Provide cut sheets for the water meter and the reduced pressure backflow preventer showing their respective pressure drops at the projected demand. Reference Section 610.2, UPC 1994.
5. Confirm the developed length for the water piping. Revise the water calculations as required.
08/11/2005 ROBERT SHERRY WATER REVIEW Approved
08/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for the addition. Reference Section 101.3, International Energy Conservation Code 2000.
2. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2000.
3. Clarify the outside air requirements for AC-1 as shown on Compliance Schedule (i.e. 175 CFM or 400 CFM).
08/19/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/31/2005 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation & 5th floor par/non-par evaluation.
09/07/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Sheet P-1, design anchors for waterheater. Provide
engineering calcs for the anchors.
09/09/2005 DAN CASTRO ZONING REVIEW Denied Zoning Review may not approve the building plans prior to stuructural review approval.
10/17/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please modify the 70/2 CB on Panel A to "70/3."
2. According to Sheet P-1 the WH is 2.0 KW, not 2.4KW, which would require a smaller OCPD, 25A, not 30A. Coordinate with Plumbing and clarify.
3. It is unclear which lighting fixtures are to go on Ckt 23, and which go on Ckt 25. This run appears twice on the plans, and one of them could be intended for Ckt 27.
4. It appears that the Grounding Electrode Conductor should be #4, not #6.
5. If the existing service is overhead, please indicate such on the plans. If this is not the case, provide an underground service.
6. This is not a Code issue, but please note that full cutoff lighting fixtures installed under canopies shall not be counted in determining total light output. Reference Tucson Lighting Code 5.1.2.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2005 JMORALE1 OUT TO CUSTOMER Completed
09/09/2005 SUE REEVES REJECT SHELF Completed