Permit Number: T05CM02695
Parcel: 12412293A

Address:
301 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02695
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/13/2005 HEATHER THRALL ZONING REVIEW Approved
06/15/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the arrangement of the existing vault and keynote #3 on sheet G-3. Provide a detail of the proposed construction.
2. Show that the new sewer complies with the requirements of Section 313.0, UPC 1994.
06/15/2005 ANY BUILDING-COMMERCIAL REVIEW Passed
06/15/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the ADA restroom ventilation complies with Section 403.3, IMC 2000.
06/15/2005 JIM EGAN FIRE REVIEW Approved
06/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
06/17/2005 GBONILL1 WWM REVIEW Needs Review
06/17/2005 GBONILL1 WATER REVIEW Needs Review