Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM02681
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | ELEC & PLUMB SCH - CALL FOR CLOSED WASHER, DISPOSAL- NOT SHOWN IN DRAWINGS |
| 07/29/2005 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS for Activity # T05CM02681 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on the original tracings and two new sets of drawings shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. FLOOR PLANS: 1. Note that stair width (minimum 36" per 311.5.1), shall be maintained at the location of the second floor a/c heat pump. ELEVATIONS: 1. Second floor ceiling gypsum board shall be either 5/8" or ½" sag resistant when applied to 24" o.c. framing Table R702.3.5 footnote d. SECTIONS - DETAILS - MISC. NOTES: 1. Identify the beam size, Framing Keynote #2, sheet A-3. 2. All wood-framing members that rest on concrete including the stairway cleat shall be protected against decay R319.1. 3. Projections shall not extend to a point closer than 2 feet from the property line, and when extending into the 3 foot fire separation distance shall have not less than one-hour fire-resistive construction on the underside. Provide notation showing compliance with R302.1. 4. Note the distance between building overhangs. The one-hour fire-resistive construction on the underside is necessary if less than 6'. 5. Correct the 1" gap between wall and fur-out pointer, Detail #6, sheet A-3. PLUMBING PLANS: 1. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code. 2. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down. 3. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type. 4. Hose bibs require backflow preventers per UPC 603. MECHANICAL PLANS: 1. Show exhaust fan locations and CFM rates for bathrooms per R303.3 and M1506. ELECTRICAL PLANS: 1. Provide an exterior outlet at grade level located at the front of the dwelling, per E3801.7. These outlets shall be GFCI protected per E3802.3. 2. Note that two or more 2O AMP small appliance circuits shall be provided to serve all receptacles outlets in the kitchen, breakfast room and dining room. Such circuits shall have no other outlets, per E3603.2 and E3801.3 through E3801.4.5. 3. Provide a note indicating only approved outlet boxes shall be used for ceiling fans, per E4001.6. 4. Show compliance with City of Tucson Outdoor Lighting Code (www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf). 5. Provide cut sheets of chosen lights. If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/12/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 08/12/2005 | SUE REEVES | REJECT SHELF | Completed |