Permit Number: T05CM02665
Parcel: 127042770

Address:
4949 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02665
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2005 JIM EGAN FIRE REVIEW Approved
06/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a complete plumbing plan.
06/10/2005 TERRY STEVENS ZONING REVIEW Approved
06/10/2005 ROBERT SHERRY WATER REVIEW Approved
06/10/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
06/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/14/2005 JMORALE1 BUILDING-COMMERCIAL REVIEW Needs Review
06/14/2005 JMORALE1 WWM REVIEW Needs Review
06/14/2005 JMORALE1 ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02665 DENIED 6/10/05

1. Provide power requirements for new Water Heater on Plumbing Plans.
2. There is one receptacle on Sheet E1.1 without power on panel schedule.
3. Correct Ckts on Panel A, 14, 16, 18, 20, & 22. Load calcs new review.